RUN |
This is not an error. Everything o.k. |
RN1 |
ADC-overflow --> This means the sensor is not covered with product and the measured results are not valid. (For example an empty pipe). Pipes and liquids only. |
RN2 |
The measured attenuation has crossed the entered thresholds and the current output is clamped to 0/4mA. |
RN3 |
The measured Brix value has crossed the Brix-Max threshold and the output is clamped to 0/4mA. |
RN4 |
Evaluation of the raw phase is unstable. If this occurs the actual measuring value is rejected and the output is kept on the last valid value. |
RN5 |
Evaluation of the raw phase is unstable. If this occurs the actual measuring value is rejected and the output is kept on the last valid value. |
RN6 |
The measured value has crossed the min. threshold of the valid measuring range. the actual measuring value is rejected and the output is hold on the last valid value. |
RN7 |
The measured value has crossed the max. threshold of the valid measuring range. the actual measuring value is rejected and the output is hold on the last valid value. |
RN8 |
T3 is active (if relay is used for timing functions). |
RN9 |
External HALT is active. (contact closed) |
RNA |
The load is smaller than Load-Min.. |